Data information
Summary
This strategy balances automation with human control. It avoids common pitfalls such as nuisance switching and ensures a predictable, user-friendly lighting experience.
Introduction
This document outlines the standard lighting control logic and behavioural rules for Loxone-based systems. It is intended as a baseline for consistent implementation across projects, ensuring reliable operation, user control, and avoidance of common automation conflict
Equipment
Loxone Config and Motion sensors
Detailed Description
Control Logic Definitions
MOET – Delay After Motion Lost
Maintains the lighting ON state for a predefined duration after motion is no longer detected.
- Prevents abrupt darkness
- Adjustable timeout depending on space usage (e.g. circulation vs lounge)
MET – Countdown When Manually Switched Off
Triggers a countdown period when lighting is manually switched OFF.
- Prevents immediate reactivation by motion
- Acts as a soft override period
- Typical use: bedrooms, lounges, cinema rooms
PTO – Prevent Turn-On After Manual Override
Disables motion-triggered activation after the user has manually switched OFF the lighting.
- Ensures user intent is respected
- Avoids “false-on” behaviour from minor movement
- Essential for user trust in automation systems
P/2 – Individual Circuits for Motion Sensors
Separates motion detection inputs across individual lighting circuits.
- Enables zoning within a space
- Allows selective activation (e.g. pathway lighting only)
- Improves energy efficiency and lighting hierarchy
Findings / Summary
Use with Presence function block for rooms and direct Mo – Motion tab on lighting controller for Toilet and Utility. Confirm timeout values with client expectations. Coordinate with scene settings and dimming curves. Ensure integration with control systems (e.g. keypads, app control)Test manual override behaviour thoroughly on site
Conclusion
Residential lighting schemesCirculation areas (hallways, stairs)Bathrooms and ensuitesCommercial spaces with occupancy-based control
Results
Image references – Top
1.1
Image references – Bottom gallery
1.2,1.3.1.4
External references